Thursday, 25 June 2015

Preliminary Design Specs

Inverter, Charge Controller, Back-up Generator and Array Design

Design parameters
Parameter
Size
 Note



1 DoA Battery requirement3.05 kWh
4 DoA Battery requirement12.19 kWh
Number of batteries8Rolls 184 Ah C10,
4 parallel x 2 series = 48V and 368 Ah
Battery energy storage17.7 kWh ~ 5 DoA
Inverter3.0 kWVictron Multiplus
Generator Size2.5 kW
Worst month array nominal size5.75 kWp
Compensated array size (due to 5 DoA and Generator)3.0 kWp
Number of modules12
Vmax per module47 V
Vmin per module25.08 V
Max current per module9.98 A
Number of strings4
Number in series3
Array Vmax141 V
Array Vmin75.24 V
Array max current39.92 A
Charge Controller3.5 kW, 150 VConext MPPT 60 PV MPPT

Basic Schematic of System